Skip to main content

Product Specifications

CO2 Sensing

ParameterDescription
Range0 – 40,000 ppm (MacSync-LCO21)
400 ppm – 2’000 ppm (± 50 ppm + 5% of reading) (MacSync-LCO22)
400 ppm – 5’000 ppm (± 40 ppm + 5% of reading)(MacSync-LCO23)
Repeatability± 10 ppm
Response time(Sensor)60 s
Additional accuracy drift per year± (5 ppm + 0.5 % of reading)
CalibrationFactory calibrated

Temperatue Sensing

ParameterDescription
Range- 10°C – 60°C
Accuracy± 0.8 °C
Resolution± 0.1°C
CalibrationFactory calibrated
Accuracy drift< 0.03 °C / year

Humidity Sensing

ParameterDescription
Range0% to 100% RH
Accuracy10% to 90% RH: ±3% RH & < 10% or > 90% RH: ±5% RH
Resolution0.5% RH
CalibrationFactory calibrated

LoRaWAN Wireless Transmission

ParameterDescription
TechnologyLoRaWAN® ( v1.0.4), Macnman Beam Protocol
AntennaInternal high- efficiency antenna
Sensitivity-137 dBm @ 300 bps
Tx Power16 dBm @868 MHz 20 dBm @915 MHz 19 dBm @470 MHz
LoRaWAN ClassClass A (default), Configurable to Class C via Maya
FrequencyIN865 , US915 , EU868 , AU915
Activation TypeOTAA

Power Specifications

ParameterDescription
Operating Voltage12-24 DC
Power consumption < 0.2 W (Typical)
Power Input TypeTerminal (Internal)
Reverse ProtectionYes
Battery OptionOptional

Physical Characteristics

ParameterDescription
Power Supply1 × 19,000 mAh Li-SOCl₂ battery (field-replaceable)
Battery Life*Up to 10+ years (SF7, 10-minute interval) & ~5.8 years (SF10, I N865)
Weight460 gms (with battery)
Ingress ProtectionIP 65 standard (IP 6 7 optional variant)
Housing MaterialGlass Field Nylon
ColorMatte W hite
Probe MaterialSteel & Plastic

Operating Conditions

ParameterDescription
Operating temperature - 35 °C , + 60 °C
Storage temperature - 40 °C , + 70 °C
Relative Humidity95% (non-condensing)
Casing BuiltSuitable for the indoor & outdoor harsh environements

Default Paramters

ParameterDescription
Frequency PlanIN868
Adaptive data rateOn
Confirmed UplinksOff
Update Interval10 Mins

Certifications

ParameterDescription
RegulatoryWPC
EnvironmentalRoHS compliant