MacSync-L-RTDX5 Datasheet
Product Overview
MacSync-L-RTDX5 is a next‑generation LoRaWAN® RTD temperature sensor engineered for ultra‑precise thermal monitoring in the most demanding industrial environments. Designed to support PT1000 probes and IEC 60751 standard linearization, it ensures highly accurate and repeatable temperature measurement from –200 °C to +850 °C, covering cryogenic, processing, and high‑temperature applications.
With industrial‑grade shielding, low‑noise analog front‑end, and minimal drift, the MacSync‑L‑RTDX5 delivers dependable performance in reactors, chemical process lines, oil & gas pipelines, cold‑storage logistics, and power utility infrastructures.
The device features Class A/C LoRaWAN® communication, a high‑efficiency internal antenna, secure AES‑128 encrypted transmission, and support for the Maya App (BLE) for rapid onboarding, OTA parameter updates, and diagnostic insights — eliminating manual configuration in remote deployments.
Its rugged IP65‑rated enclosure, stainless‑steel probe compatibility (SS304 / SS316), multi‑year battery operation, and optional external DC power input make it a long‑life sensor designed to thrive in harsh industrial and outdoor environments.
Whether used for predictive maintenance, compliance monitoring in pharma logistics, or thermal safety in high‑temperature industrial processes, MacSync‑L‑RTDX5 transforms any RTD probe into a smart, wireless, and future‑ready IoT sensing node, enabling Industry 4.0 automation and operational excellence.
![]() | ![]() |
|---|---|
![]() | ![]() |
Download Center
Download the PDF Version of the Datasheet .
Click here to view the decoders for MacSync-L-RTDX5
Key Features
High‑Accuracy RTD Input Compatible with PT1000 probes for precise industrial temperature monitoring.
Wide Temperature Range Supports –200 °C to +850 °C for cryogenic, process, and high‑temperature environments.
Industrial‑Grade Reliability Low noise, low drift, and high repeatability for mission‑critical applications.
Ultra‑Low Power LoRaWAN® Multi‑year battery life with Class A/C support for long‑range connectivity.
Rugged & Ingress‑Protected Enclosure IP65/IP67 protection for harsh outdoor and industrial deployments.
BLE Configuration via Maya App Fast onboarding, OTA parameter tuning, and diagnostics using a smartphone.
SS304 / SS316 Probe Support Corrosion‑resistant stainless‑steel probe options for chemical and process industries.
Smart Uplink Strategies Periodic, event‑based, or threshold reporting to extend battery performance.
Secure Data Communication AES‑128 encrypted LoRaWAN® connectivity ensuring industrial‑grade security.
Industrial IoT Platform Integration Works with all major LoRaWAN® network servers and cloud systems.
Flexible Deployment Supports internal or external RTD probe installation for diverse monitoring needs.
Future‑Proof Design Ideal for Industry 4.0 modernization and remote thermal analytics.
Suited Applications
Industrial Process Temperature Monitoring Highly accurate RTD sensing for reactors, tanks, kilns, ovens, boilers, and thermal processing equipment.
Oil & Gas Pipeline Monitoring Real-time temperature tracking to detect leaks, overheating, and pipeline integrity issues.
Chemical & Petrochemical Plants RTD probes withstand aggressive chemicals and corrosive environments for safe temperature control.
Cold Chain & Pharmaceutical Storage Regulatory-compliant monitoring for vaccines, biologics, perishable goods & medical refrigeration.
Energy & Power Utilities Thermal supervision for substations, transformers, turbines, heat exchangers, and district heating.
Steel, Foundry & Mining Operations High-temperature safety monitoring near furnaces, smelters, mines, and metallurgical processes.
HVAC & Industrial Cooling Systems Performance monitoring for chillers, heat pumps & climate control industrial systems.
Remote Industrial Assets Reliable LoRaWAN® connectivity in isolated and hazardous locations where wired sensors fail.
Industry 4.0 Automation Smart analytics, predictive maintenance & operational efficiency through long-range IoT sensing.
Technical Specification
General
Specifications
Part Order Number
MacSync-L-RTDX5
Product Brand
Macnman Technologies Pvt Ltd
Temperature
Measurement
Sensor Type
RTD (PT1000)
Range
–200 °C to +850 °C
Accuracy
±0.2 °C (typical)
Resolution
0.1 °C
Repeatability
±0.05 °C
Probe Options
Internal & External Both Options
Sensor Linearization
IEC 60751 standard curve
Self‑Heating Error
< 0.1 °C @ 1 mA excitation
Drift (1 Year)
< 0.05 °C
Insulation Resistance
> 100 MΩ @ 500 VDC
Probe Material
SS304 / SS316 (optional)
Wireless
Transmission
Wireless Protocols
LoRaWAN® (v1.0.4)
Macnman MacTalk Protocol
Antenna
Internal high-efficiency antenna
Supported Bands
IN865 / RU864 / EU868 / US915 / AU915 / KR920 / AS923-1/2/3/4
Tx Power
23 dBm @ 868 MHz / 20 dBm @ 915 MHz / 19 dBm @ 470 MHz
Sensitivity
-137 dBm @ 300 bps
Activation
OTAA
LoRaWAN® Class
Class A (default)
Configurable to Class C via Maya
LED
Status
LED Type
1 Internal Multi-Color LED
Solid Blue
Device is connected with Maya App
Flashing Blue
OTA (Over-the-Air) update in progress
Slow Blinking Green
Attempting to connect to the LoRaWAN® network
Single Red Blink
A confirmed parameter of MacSync is being modified
Device
Configuration
Configuration
Via Macnman Maya Android App
Uplink Modes
Time Based / Threshold Based / Sampling Based
Stored Records*
30,000 Records
Remote Configuration
JSON Format Data - from server
Battery
Performance
Battery Type
Li-SOCl₂ Cell (19Ah) Industrial grade
Power Consumption
~100 µA in sleep mode
~50 mA during transmission
Battery Life
Up to 10 years (10 Mins Uplink Interval)
Supported
LNS
Supports Major LNS
Private LNS
Chirpstack
The Things Networks
MQTT
Orbiwise
LORIOT
Direct PLC On-Prim Installations
Physical
Characteristics
Power Supply (Optional)
9-36 V DC
Operating Temperature
-40°C to +80°C
Humidity Range
0% to 100% RH (non-condensing)
Ingress Protection
IP65 standard (IP67 optional variant)
Housing Material
Glass field Nylon
Color
Matte White
Weight
~110g
Mounting Options
Pole Mounting / Wall Mounting
Electrical
Characteristics
Input Voltage Range (Optional Varient)
9-36 V DC (External Supply)
Power Consumption
~100 µA in sleep mode
~50 mA during transmission
Input Impedance
>10 MΩ for voltage inputs
Communication
Options
BLE Connectivity
For local configuration and diagnostics via Maya App
Cloud Protocols
MQTT / HTTPS / TCP IP (Gateway Dependent )
Serial Interface
RS485 Modbus RTU support (optional)
Certifications &
Compliance
WPC
Compliant
RoHS
Conforms to RoHS directive
Security &
Encryption
Data Encryption
AES-256 end-to-end encryption
Authentication
OTAA activation modes
Firmware Protection
Secure boot and signed OTA updates
MacSync-L-RTDX5 Variants
| Variant Name | Power Source | Battery Capacity | Solar Support | External Flash | Ideal For |
|---|---|---|---|---|---|
| MacSync-L-RTDX1-PO | 12–24 V (Power) | ✖️ | ✖️ | ✔️ | Industrial or commercial sites with stable power supply |
| MacSync-L-RTDX1-BO | Battery | 19 Ah | ✖️ | ✔️ | Remote or portable deployments with low power |
What's in the box ?
Make sure box contains following items before installations
Accessories must be purchased separately & may not be included in the box.